FLUKE

Clamp On Earth Resistance Tester, 0.025 to 1500 ohm Ground Resistance Range, 1.38" (35mm) Jaw Capaci

  • Item# 1CWL8
  • Mfr. Model# FLUKE-1630
  • Catalog Page# 705
  • UNSPSC# 41113648
Clamp On Earth Resistance Tester, 0.025 to 1500 ohm Ground Resistance Range, 1.38" (35mm) Jaw Capaci close
close x

Using 360° Viewing:

  1. Rotate: Use top-to-bottom, side-to-side by use of mouse arrow.
  2. Zoom In: Double click on image.
  3. Zoom Out/Reset: Put photo at full zoom & then double click.
Megaphone How can we improve our Product Images?

Price $1,980.00 / each

Activate Now

to save with

Select AdvantageSM

Please sign in or register to access lists

Please sign in or register to access Quote

Jump to:
  • Shipping Weight 4.56 lbs.
Country of Origin Taiwan Country of Origin is subject to change.
Note: Product availability is real-time updated and adjusted continuously. The product will be reserved for you when you complete your order. More

Product Details

Provides frontline troubleshooting and in-depth soil analysis—a complete solution for utilities, electrical contractors, industrial facilities, telecom, and data centers. Features calibration resistance test loop and adjustable limits for fast testing.

View More

Technical Specs

  • Item Clamp On Earth Resistance Tester
  • Ground Resistance Range 0.025 to 1500 ohm
  • Jaw Capacity 1.38" (35mm)
  • Resolution 0.002 to 20 Ohms
  • Operating Frequency 3333 Hz
  • Current Measurement Range 0.20 to 30A AC
  • Display Digital LCD
  • Counts 9999
  • Resistance Accuracy From +/-1.5% of Reading +/-0.05 to +/-20% Dependent on Range
  • Auto Power Off Yes
  • Data Logging 116 Readings
  • Battery Type 9V
  • Safety Rating CAT III 300V
  • Includes Carrying Case With Strap, Battery, Resistance Test Loop and Instructions
  • Manufacturers Warranty Length 2 yr.
Megaphone How can we improve our Technical Specifications?

Compliance and Restrictions

None

Alternate Products

Alternate Products may not be identical in style or function to original selection. Please compare below for more information.

Customer Reviews


Rated 5 out of 5 by 1reviewer.
Rated 5 out of 5 by Remember to use it with Main Bounding Jumper set Check the Principles of Earth Grounding 3, 0:53 video. It's showing a fluke 1630 shown a reading over an GEC not with being connected to a MBJ. This is an big mistake in that Fluke 1630 only reads on a Earth Ground Loop circuit. There must be a ground loop before you can measure Resistance, therefore you need another GEC made to the center tap of a transformer or other generator device.I apreciate all your presentation videos. February 2, 2015
  • 2015-09-08T19:47:51.930-05:00
  • bvseo_lps, prod_bvrr, vn_prr_5.6
  • cp-1, bvpage1
  • co_hasreviews, tv_1, tr_1
  • loc_en_US, sid_1CWL8, prod, sort_default
1-1 of 1

Product Reviews Disclaimer:
Grainger is neither responsible for, nor does it endorse, the content of any product review or statement posted. Any statements posted constitute the statements of the poster and are not the statements of Grainger. The statements posted by Grainger employees with the Grainger employee badge represent the views of such employees and are not the statements of Grainger. Grainger makes no representations as to the appropriateness, accuracy, completeness, correctness, currentness, suitability, or validity of any product review or statements posted, including those posted by employees with the Grainger employee badge, and is not liable for any losses, injuries or damages which may result from any such product review or statements. Use of any linked web site provided in a product review or post is at the user's own risk.