| Item | Supply Ventilator | |
| Type | Direct Drive Downblast | |
| Propeller Dia. (In.) | 14 | |
| CFM @ 0.000-In. SP | 2586 | |
| CFM @ 0.125-In. SP | 2395 | |
| CFM @ 0.250-In. SP | 2176 | |
| CFM @ 0.375-In. SP | 1971 | |
| CFM @ 0.500-In. SP | 1799 | |
| CFM @ 0.625-In. SP | 1588 | |
| CFM @ 0.750-In. SP | 1380 | |
| Sones @ 0.125-In. SP @ 5 Ft. | 19.8 | |
| Sones @ 0.250-In. SP @ 5 Ft. | 19.9 | |
| Voltage | 115 | |
| Hz | 60 | |
| Phase | 1 | |
| Max. Operating Amps | 4.8 | |
| Motor HP | 1/2 | |
| Max. BHP | 0.46 | |
| RPM | 1750 | |
| Max. Inlet Temp. (Deg. F) | 120 | |
| Base Width (In.) | 22 | |
| Base Length (In.) | 22 | |
| Base Height (In.) | 1 3/4 | |
| Base Top to Shroud (In.) | 6 1/4 | |
| Overall Height (In.) | 16 1/2 | |
| Overall Dia. (In.) | 28 5/8 | |
| Mounting Location | Roof | |
| Housing Material | Spun Aluminum | |
| Propeller Material | Aluminum | |
| Shaft Dia. Propeller End (In.) | 1/2 | |
| Speed Control | 1DGV3 | |
| Speed Controllable | Yes | |
| Agency Compliance | UL 705 | |
| Requires | Roof Curb For New Installations | |
| Includes | NEMA 1 Junction Box | |
| Adj. 12 3/8"H Roof Curb Stock No. | 2ZV82 | |
| Adj. 6 3/8"H Roof Curb Stock No. | 4C453 | |
| Recommended 12 In. Fixed Curb Item No. | 2RB76 | |
| Recommended 8 In. Fixed Curb Item No. | 4HX39 | |
| Recommended Damper Size (In.) | 15 x 15 | |
| Recommended Damper Stock No. | 4HX65 |
** The "Usually Ships" reflects when an item is generally expected to ship from Grainger based on its stocking location. Real-time availability information will be shown during the checkout process and on the e-mail order confirmation (for U.S. and Puerto Rico - US customers only). Please allow additional delivery time for international orders.