Auto Standby Generator,Air Cooled,10kW

Automatic Standby Generator, EmPower(TM) Series, Air Cooled, 10 kW, Amps @ 120/240V, 1 Phase LP 100.0/50.0 (NG 91.6/45.8), NG Load Consumption 84 @Half Load Cu-Ft/Hr, Propane Load Consumption 34.19 @Half Load Cu-Ft/Hr, Propane Load Consumption 0.94 @ Half Load GPH, Min Gas Pressure @ Generator 5-7 in NG 11-14 LP In WC, Engine Size 570cc, Battery Requirements Min Amp Hr 90, Battery Requirements Group 26, Battery Requirements 12 Volts, Includes 50 Amp Automatic Transfer Switch
Grainger Item # 2FCB9  
Price (ea.) $3,309.00
Brand BRIGGS & STRATTON  
Mfr. Model # 40246  
Ship Qty. 1  
Sell Qty. (Will-Call) 1  
Ship Weight (lbs.) 353.0  
Usually Ships** 1-3 Days  
Catalog Page No. 1092 catalog  
See Notes & Restrictions for important safety information.
Qty.
  • Add to Order
  • Add to Personal List
  • Compare Alternate Items
Price shown may not reflect your price. Log in or register.
Item Automatic Standby Generator
Type EmPower(TM) Series, Air Cooled
kW 10
kVA Rating 10,000
Voltage 120/240
Amps @ 120/240V, 1 Phase LP 100.0/50.0 (NG 91.6/45.8)
Fuel Natural Gas/ LP Vapor
NG Load Consumption (Cu.-Ft./Hr.) 84 @ Half Load
Propane Load Consumption (Cu.-Ft./Hr.) 34.19 @ Half Load
Propane Load Consumption (GPH) 0.94 @ Half Load
Min. Gas Pressure @ Generator (In WC) 5-7 NG 11-14 LP
Engine Brand Briggs and Stratton Vanguard
Engine (Cooling) Air
Engine (Block Heater) No
Engine RPM 3600
Engine Size 570
Automatic Volts Regulation Yes
Battery Requirements Min. Amp Hr. 90
Battery Requirements Group 26
Battery Requirements (Volts) 12
12VDC Battery Charger Yes
Fault Indicator Lights 1
Repeat of Exercise Cycle 7
Low Coolant Level No
High Temp. Yes
Low Oil Pressure Yes
Over Crank Protection Yes
Over Speed Yes
Main Circuit Breaker Included
Phase Single
Power Factor 1.0
Run Time Hour Meter Yes
Sound Level dBA 75
Length (In.) 32
Height (In.) 35
Width (In.) 39
Fuel NPT Pipe Connection Sz. 3/4" NPT
Includes 50 Amp Automatic Transfer Switch
Function Produce Emergency Electric Power During Utility Power Failures to Keep Essential Heating/Cooling Systems, Pumps, Lighting and Office Equipment Operating
Housing Weather Resistant, Sound Dampening, All Metal Enclosure
Installation Require Local Permits for Gas Piping, Electrical Inspection and Approval
Agency Compliance NEC/UL2202

** The "Usually Ships" reflects when an item is generally expected to ship from Grainger based on its stocking location. Real-time availability information will be shown during the checkout process and on the e-mail order confirmation (for U.S. and Puerto Rico - US customers only). Please allow additional delivery time for international orders.